ISO 9001:2015 · ISO 22000:2018 · ISO 14001:2015🛒 Online Store ↗
ZEEL PRODUCT Z logoZEEL PRODUCT®ZEELCHEM® · Water Treatment Chemicals
Get a Quote
Boiler Water · 05 October 2026

Hydrazine Hydrate as an Oxygen Scavenger in Boilers

How hydrazine hydrate removes dissolved oxygen from boiler feedwater, dosage calculation, passivation benefits and safe handling.

Quick answer: Hydrazine hydrate reacts with dissolved oxygen to form only nitrogen and water, so it removes O₂ without adding dissolved solids – ideal for high-pressure boilers. Dose about 1.5–2 ppm hydrazine per ppm of oxygen plus a small residual.

Reaction

N₂H₄ + O₂ → N₂ + 2H₂O. Hydrazine also converts red iron oxide to protective black magnetite, passivating boiler steel.

Dosage example

Feedwater with 0.02 ppm O₂ after deaeration, flow 20 m³/h: 0.02 × 2 = 0.04 ppm hydrazine + 0.05 ppm residual ≈ 0.09 ppm → about 1.8 g/h hydrazine.

Safety

  • Toxic and a suspected carcinogen – closed dosing systems and full PPE.
  • Many plants now use DEHA or carbohydrazide as alternatives.

See all boiler water treatment chemicals.

#hydrazine hydrate#oxygen scavenger#boiler feedwater

Frequently asked questions

Why is hydrazine used in boilers?

It removes dissolved oxygen without adding solids and forms a protective magnetite layer on steel.

What is the hydrazine dosage for boilers?

About 1.5–2 ppm hydrazine per 1 ppm dissolved oxygen, plus a feedwater residual of roughly 0.02–0.1 ppm.