Cycles of Concentration in Cooling Towers: Formula & Calculation

How to calculate cycles of concentration (COC) in a cooling tower, make-up and blowdown formulas, and how higher COC saves water.

Quick answer: Cycles of concentration (COC) = conductivity (or chloride) of tower water ÷ conductivity of make-up water. Blowdown = evaporation ÷ (COC − 1). Raising COC from 3 to 6 cuts blowdown by about 60%, saving water and chemicals.

Formulas

ItemFormula
COCTower conductivity ÷ make-up conductivity
Evaporation (m³/h)≈ Circulation × ΔT(°C) × 0.00153
BlowdownEvaporation ÷ (COC − 1)
Make-upEvaporation + blowdown

Worked example

Circulation 500 m³/h, ΔT 6 °C → evaporation ≈ 4.6 m³/h. At COC 3, blowdown = 2.3 m³/h; at COC 6, blowdown = 0.92 m³/h – saving about 33 m³ per day.

How to run higher cycles safely

Use a stronger scale inhibitor and dispersant such as PAPEMP with terpolymer, and check the LSI.

#cycles of concentration#COC calculation#cooling tower blowdown

Frequently asked questions

How do you calculate cycles of concentration?

Divide the conductivity (or chloride) of recirculating water by that of the make-up water.

What is a good COC for a cooling tower?

Typically 3–6, depending on make-up quality and the treatment programme.