The principle
Orthophosphate is an anodic corrosion inhibitor. It forms a protective iron phosphate/oxide film on mild steel. At useful levels it would normally precipitate with calcium, so a stabilising polymer is essential. Phosphate stays soluble in the bulk water and is available at the metal surface.
Typical control ranges
| Parameter | Range |
|---|---|
| Orthophosphate (PO₄) | 6 – 15 mg/L |
| Total inorganic phosphate | Ortho + 1 – 3 mg/L |
| pH | 7.2 – 8.2 |
| Ca hardness | < 800 mg/L as CaCO₃ (higher with more polymer) |
| Polymer (terpolymer product) | 1.5 – 2.5 × PO₄ |
| Azole (for copper) | 1 – 3 mg/L |
Choosing the stabiliser
Terpolymer gives the widest operating window: higher pH, calcium and temperature. AA/AMPS is a cost-effective alternative at moderate stress. Plain PAA is not suitable as the main stabiliser. See why calcium phosphate forms.
Start-up and passivation
- Clean the system (acid or neutral cleaning, as needed).
- Passivate with 2–3 times the normal phosphate level for 3–5 days, keeping the polymer ratio.
- Reduce to the maintenance level and establish cycles and pH control.
Monitoring
- Ortho- and total phosphate: a falling ortho with steady dosing suggests precipitation.
- Filtered vs unfiltered phosphate.
- Corrosion coupons (90-day) and on-line corrosion probes.
- Polymer residual, or an inert tracer.
Phosphate sources, azoles and biocides are in the ZEELCHEM™ range. For plants with phosphorus discharge limits, consider the non-phosphorus alternative.
FEATURED PRODUCTZEELCHEM™ 7000 – Terpolymer
Three-monomer terpolymer for the toughest cooling water: high cycles, high pH, phosphate, zinc and iron together.
FAQ
What pH range suits a phosphate program?
Typically 7.2–8.2.
How much terpolymer per ppm of phosphate?
About 1.5–2.5 mg/L product per mg/L orthophosphate.
Why passivate at start-up?
To build the protective film quickly before normal maintenance levels.
More from ZEEL PRODUCT: zeelproduct.com · zeelproduct.net · ZEELCHEM™ range · online shop · zeelproductonline.co.in