Quick answer: Cycles of concentration (COC) = make-up ÷ blowdown, or basin TDS ÷ make-up TDS. Raising COC from 3 to 6 cuts blowdown by 60 % and make-up by about 20 %. High cycles are limited by CaCO₃ (LSI), silica, calcium phosphate and chloride, and a high-performance terpolymer (ZEELCHEM™ 7000) is often what makes 6–10 cycles possible.

The water-saving maths

Evaporation is fixed by the heat load. Blowdown B = E ÷ (COC − 1), so make-up M = E × COC ÷ (COC − 1).

COCBlowdown (per 100 m³ evaporated)Make-up
2100 m³200 m³
350 m³150 m³
433 m³133 m³
620 m³120 m³
814 m³114 m³
1011 m³111 m³

Going from 3 to 6 cycles saves 30 m³ of make-up for every 100 m³ evaporated. For a 500 m³/h tower, that is hundreds of thousands of m³ a year. Blowdown also carries chemical, so the treatment chemical demand falls too. Check your numbers with the cooling tower calculator.

What limits cycles

  • Calcium carbonate: LSI rises with cycles. See LSI.
  • Silica: roughly 150–200 mg/L. See silica control.
  • Calcium phosphate: where recycled water carries phosphate.
  • Calcium sulphate at high sulphate.
  • Chloride and TDS: corrosion of steel and stainless steel.
  • Suspended solids and biofouling: longer residence time.

How a terpolymer helps

At high cycles, several deposits approach their limits at once. ZEELCHEM™ 7000 terpolymer stabilises carbonate, phosphate, iron and silt together and has very high calcium tolerance. Combined with PBTC and good biocide control, it lets many systems move from 3–4 cycles to 6–8.

Steps to raise cycles safely

  1. Analyse make-up water and identify the first limiting species.
  2. Upgrade the treatment program (terpolymer + PBTC + azole + biocide).
  3. Add side-stream filtration for suspended solids.
  4. Raise cycles in steps of 0.5–1, monitoring calcium balance and coupons.
  5. Automate blowdown on conductivity.
Terpolymer 3D ball-and-stick molecular structure – ZEELCHEM™ 7000 water treatment polymer by ZEEL PRODUCT, VadodaraFEATURED PRODUCT

ZEELCHEM™ 7000 – Terpolymer

Three-monomer terpolymer for the toughest cooling water: high cycles, high pH, phosphate, zinc and iron together.

FAQ

What is a good cycles of concentration?

Many Indian systems run at 3–5. With good treatment, 6–8 is achievable depending on water quality.

How do I measure COC?

Divide basin conductivity (or chloride or magnesium) by the make-up value.

Does higher COC save chemicals?

Yes. Less blowdown means less chemical is lost.

ZP
ZEEL PRODUCT Technical Team
Water treatment chemists at ZEEL PRODUCT, Vadodara. ISO 9001:2015 certified manufacturer of ZEELCHEM™ polymers.

More from ZEEL PRODUCT: zeelproduct.com · zeelproduct.net · ZEELCHEM™ range · online shop · zeelproductonline.co.in

Related articles

Need a polymer for your water system?

Share your water analysis and system details. Our technical team will recommend the right ZEELCHEM™ polymer and dosage, and send today's price with TDS, MSDS and COA.